Supporting up to 1000 Amps, Roam's MTC® 6003 OES10KvB series ("v" = Voltage Code) of Power Output Panels provides a rugged and cost-effective, exterior connection point for high-capacity external power loads. Roam's 1000A Power Output Panels use E1016 (J-Series/16 Series) Female Cam-Lok* connectors in three rows of 400A (max) connectors bus-barred together allows the panel to support up to 1000A.
The standard in safety and outdoor reliability, Roam's line of Power Output Panels makes connecting building (line) power to external or internal loads fast, easy, and most importantly—safe.
Roam's 1000A Power Output Panels are functionally identical to our 1200A (max) Generator Panels (docking stations). The maximum amperage that the Series-16 Cam-Lock connectors can handle is 400A each, so any panel that needs to support over 800A and up to 1200A must use three rows of Cam-Lock connectors that are bus-barred together.
Roam's MTC 6003 OES10KvB 1000 Amp Power Output Panels accept either #2 to 2/0 or 2/0 to 4/0 cables via Cam-Lock plugs on the output cable side, and from #2 AWG to 600MCM cables on the internal wireway side. The wireway connection supports up to dual 600MCM cables (via bolted on lugs) on internal bus bars.
Roam offers the MTC 6003 OES10KvB Power Output Panel in models that support up to 240 VAC (120v, 208v, 230v, 240v)—MTC 6003 ES10K2B, up to 480 VAC (277v, 330v, 440v, 480v)—MTC 6003 OES10K4B-BOY, and up to 600 VAC (575v, 577v, 600v)—MTC 6003 OES10K6B. All of the 1000A panels are UL Listed and cUL Listed (Canada) at those voltage levels. Brown-Orange-Yellow color coding (for labels, Cam-Locks, & Cam-Lock spring caps) is normally used for most 480 VAC applications.
Any Roam panels with power connectors normally color coded (for Cam-Locks, Spring Caps, and Labels) as L1=Black, L2=Red, & L3=Blue, are also available in the typical Canadian color coding format of L1=Red, L2=Black, & L3=Blue. If you need to order a unit with the Canadian color scheme, just add a "-CAN" to the end of the Model Number. If the loads you are connecting the Power Output Panel to use the US color coding (L1=Black, L2=Red, L3=Blue), then you may want the standard US color system (so long as local electrical codes allow).
Roam's 1000A Power Output Panels (Boxes) can also be ordered with no neutral connection for site and generator configurations designed for just Ground, L1, L2, and L3 cables. The "No Neutral" versions of these panels are also UL Listed and cUL Listed (Canada). To order a panel without a neutral connector just add a "-NN" to the end of the Model Number. The "No Neutral" panels use only four sets of three Cam-Lock connectors bus-barred together (a set of three for Ground, a set of three for L1, a set of three for L2, and a set of three for L3) for a total of twelve connectors.
Base Model Number | Up to 240VAC | Up to 480VAC | Up to 600VAC | No Neutral Connector |
---|---|---|---|---|
MTC 6003 OES10KvB | MTC 6003 OES10K2B | MTC 6003 OES10K4B-BOY | MTC 6003 OES10K6B | MTC 6003 OES10KvB-NN |
The "v" in the part number represents a code of either 2 (for up to 240 VAC panels), 4 (for up to 480 VAC panels), or 6 (for up to 600 VAC panels).